product description

H Class no -encapsulated-winding dr y-type power transformers with compound cross section designed by both Shenyang Transformer Research Institute get breakthrough magnetic-circuit structure and entire layout of traditional transformers. reach international advanced level. Meanwhile, it seizes the visual advantages on the aspect of energy saving and environmental protection. This product shows balance of three-phase no-load current, less no-load loss and no-load current that are a 40% and a 80% decline respectively compared with national standard, besides, it is featured with smaller volume, lighter weight and lower noise, therefore, this product is more and more popular with customers. It is used extensively in the locations where require fireproof and explosion-proof functions, such as high -rise building, shopping center, airport, underground, station, port, petrol, chemistry engineering, nuclear power station, nuclear submarine residential area, light rail, power plant and so on.


Models and features

Types of meaning


Normal use condition
Maximum temperature: +40 ° C
Maximum daily temperature: +30 ° C
The highest annual average temperature: +20 ° C
Cooling method: AN
Minimum temperature: -30 ° C
Altitude: below 1000m
Indoor use: (plus the outer casing for outdoor use)


Performance technical indicators
Rated voltage: high voltage: 6.0, 10, 10.5, 11KV
Low voltage: 0.4KV
High voltage tapping range: +5% or 2x2.5%
Connection method: Yyn0/Dyn11
Insulation class: H class
Insulation level: LI60AC35/AC3
Sound level is: 40 - 50dB



Product Standards

GB/T 10228-2015 Dry Power Transformer Technical Parameters and Requirements
GB 1094.11-2007 "Power transformers - Part 11: Dry transformers"
GB 1094.3-2017 "Insulation horizontal insulation test and external insulation air gap"
GB/T 1094.12-2013 "Dry Power Transformer Load Guidelines"
GB 4208-2017 "Shell protection grade IP code"
JB/T 10088-2016 "6~220KV class transformer sound level"


product structure

Compared with the traditional stacked iron core, the iron core stacking has a seam, whether it is a direct grounding seam or a diagonal seam, and the seam of the silicon steel sheet forms an air gap in the magnetic circuit, so the joint is in the seam. At the high magnetic reluctance flux saturation region, the energy loss is concentrated here. If there is no seam in the iron core, there is no high energy consumption zone, and the high magnetic permeability of the high quality iron core material can be fully utilized.
The power transformer uses a wound core, which can greatly improve the magnetic circuit of the transformer by virtue of its continuous winding without seams.
DuPont NOMEX insulation winding technology is used for coil insulation structure, which makes the insulation heat resistance of the product increase to H grade and the combustible material is reduced by 80%.
The low voltage coil uses a foil coil structure.
The high-voltage coil adopts a cake-type coil structure. Since the NOMEX paper-wrapped copper wire is wound, the cakes are all made of polymer composite gaskets.
The foil type low voltage coil and the cake type high voltage coil cooperate with each other, and the leakage end resistance of the winding end is small, thereby improving the short circuit resistance of the transformer.
The high and low voltage coils use NOMEX insulation materials combined with polymer composite materials to maintain high electrical performance under both wet conditions and high temperature conditions.


Features

The three-phase current is basically balanced, and the active loss due to the three-phase current imbalance of the power grid is reduced during operation.
The iron core has no joints and is annealed. The no-load loss and no-load current are greatly reduced compared with the laminated core. The SCB9 is reduced by 30-40% and 80% respectively, achieving the purpose of energy saving.
The core has no joints, and the noise of the transformer is greatly reduced, which is 10dB lower than the conventional one, and the noise is below 50dB.
The high-voltage coil adopts the cake-type coil structure, which is wound by DuPont paper-wrapped copper wire, and the high-frequency composite material pad has the lowest partial discharge.
The foil type low voltage coil and the cake type high voltage coil are optimally combined, the leakage end resistance of the winding end is small, and the coil support pressing device is evenly distributed, so the transformer has strong short circuit resistance.
The materials used in this product are heat-resistant, flame-retardant, especially insulating materials, and have been used in the aerospace industry. This product has good high temperature resistance, fire resistance even at 800 ° C high temperature, will not release toxic or corrosive substances.
The unique process of composite coil core, the perfect combination of technology and tradition, summed up the experience of the successful operation of traditional transformers, improved the ventilation effect of the transformer itself, and achieved better heat dissipation. Therefore, the service life of the product is prolonged, the overload capacity is correspondingly improved, and the long-term safe operation can be performed under the condition of 120% overload.

Technical Parameters

SGB11-R technical parameters


额定容量 (KVA)
Rated capacity


SC9


SGB11-R

SGB11-R比SC9下降(%)
Compared with SC9, SGB11-R products declines by

空载电流(%)
No-Load
current

空载损耗(W)
No-Load
loss

空载电流(%)
No-Load
current

空载损耗(W)
No-Load
loss

空载电流(%)
No-Load
current

空载损耗(W)
No-Load
loss

噪声(%)
Noise

50

2.1

320

0.5

230

76.1

39



30

80

2.1

400

0.5

300

76.1

33.3

100

1.8

430

0.4

330

77.7

30.1

125

1.6

490

0.4

390

75

25.6

160

1.4

580

0.4

450

71.4

29

200

1.4

650

0.3

500

78.5

30

250

1.4

780

0.3

600

78.5

30

315

1.4

920

0.3

700

78.5

31.5





30

400

1.2

1050

0.3

780

75

34.6

500

1.2

1200

0.3

920

75

30.5

630

1.2

1500

0.3

1010

75

48.5

630

1

1400

0.3

1050

70

33.3

800

1

1650

0.2

1270

80

30

1000

0.8

1950

0.2

1485

75

31.3

1250

0.8

2250

0.2

1785

75

26.1

1600

0.8

2650

0.2

2050

75

29.2

2000

0.6

3600

0.2

2490

66

44.5

2500

0.6

4350

0.2

3000

66

45


Technical parameters of SGB11-R-50~2500/10 winding dry-type transformer




额定容量 (KVA)
Rated capacity

空载损耗(W)
No-Load loss

负载损耗W(145°C)
Load loss

空载电流(%)
No-Load current

声级(LPA)db
Sound level(LPA) db


阻抗电压
(%)
Impedance
voltage

国标
National standard

企标
En terprise standard

国标
National standard

企标
Enterprise standard

国标
National standard

企标
Enterprise standard

国标
National standard

企标
Enterprise standard

50

360

230

1490

1040

2.8

0.5

55

45

4

80

460

300

2150

1500

2.6

0.5

55

45

4

100

510

330

2550

1530

2.4

0.4

55

45

4

125

600

390

3050

1830

2.2

0.4

56

45

4

160

700

450

3650

2190

2.2

0.4

58

45

4

200

820

500

4680

2808

2.0

0.3

58

45

4

250

950

600

5500

3300

2.0

0.3

58

46

4

315

1100

700

6600

3960

1.8

0.3

60

46

4

400

1300

780

7800

4680

1.8

0.3

60

46

4

500

1500

920

9350

5610

1.8

0.3

62

46

4

630

1750

1010

10900

6540

1.6

0.3

62

48

4

630

1680

1050

11500

6900

1.6

0.3

62

48

6

800

2120

1270

13600

8160

1.6

0.2

64

48

6

1000

2480

1485

15700

9420

1.4

0.2

64

49

6

1250

2980

1785

18400

11040

1.4

0.2

65

49

6

1600

3420

2050

21300

12780

1.4

0.2

66

49

6

2000

4150

2490

25000

15000

1.2

0.2

66

50

6

2500

5000

3000

29100

17460

1.2

0.2

67

50

6

Dimensions


型号
Type


非封闭式(无防护外罩) No-encapsulated (without protective housing)
LxBxH



m



n



g

封闭式(有防护外罩)
Encapsulated (with protective housing)
LxBxH



M


重量 kg Weight

SG11-50/10

1120x700x1050

330

600

700

1420x1230x1330

330

600

SG11-80/10

1120x700x1050

330

600

700

1420x1230x1330

330

630

SG11-100/10

1120x700x1050

400

600

700

1420x1230x1330

400

660

SG11-125/10

1130x700x1135

400

600

700

1430x1250x1390

400

720

SG11-160/10

1150x700x1145

550

600

700

1450x1260x1400

550

830

SG11-200/10

1170x800x1160

550

700

700

1470x1260x1410

550

920

SG11-250/10

1195x800x1220

590

700

700

1500x1280x1470

590

1020

SG11-315/10

1220x800x1260

550

700

700

1520x1290x1510

550

1170

SG11-400/10

1260x900x1350

550

800

1000

1560x1310x1600

550

1480

SG11-500/10

1295x900x1455

550

800

1000

1600x1320x1710

550

1690

SG11-630/10

1451x1000x1340

660

900

1000

1720x1440x1590

660

1840

SG11-630/10

1415x1000x1340

660

900

1000

1720x1440x1590

660

1840

SG11-800/10

1475x1000x1355

780

900

1000

1780x1540x1610

780

2100

SG11-1000/10

1525x1000x1490

830

900

1000

1830x1560x1740

830

2380

SG11-1250/10

1580x1100x1510

665

1000

1000

1880x1580x1760

665

2830

SG11-1600/10

1660x1250x1570

665

1150

1000

1960x1600x1820

665

3700

SG11-2000/10

1730x1250x1715

660

1150

1000

2130x1630x1970

660

4310

SG11-2500/10

1825x1250x1760

680

1150

1000

2130x1640x2010

660

4810


Note: If the above-mentioned size change, is subject to real products.



Back to top

中御变压器

Specializing in power transformers and
supporting products Manufacturing,
research and development, product sales
as one of the high-tech enterprises
微信公众号二维码